How to choose the right surge protection device (SPD): complete selection guide
Choosing a surge protection device (SPD) isn't
simply about picking the highest kA rating. The correct selection depends on
the electrical system, installation point, expected surge exposure and
equipment being protected. IEC 61643-11:2025 sets requirements for low-voltage
AC SPDs, including performance, safety and testing.
In simple terms, the right SPD depends on where it will be
installed and what it needs to protect. For many distribution-board
applications, a surge
protection device Type 2 is commonly used, while Type 1, Type 1+2
and Type 3 devices may be needed at other points in the system.
Start with the protection point
|
SPD type |
Where it is used |
Main purpose |
|
Type 1 |
Main incoming supply |
Handles high-energy surges, including lightning-related
exposure |
|
Type 1+2 |
Main distribution point |
Combines Type 1 and Type 2 protection |
|
Type 2 |
Distribution boards |
Limits surge voltages reaching downstream equipment |
|
Type 3 |
Close to sensitive equipment |
Adds protection for sensitive electronic devices |
The table gives you the basic picture. Type 1 is used closer
to the incoming supply, Type 2 is commonly used at distribution boards, and
Type 3 provides additional protection close to sensitive equipment.
First identify where the device will be installed. Type 1
SPDs address higher-energy lightning exposure, while Type 2 devices are
commonly used at distribution boards to limit overvoltages reaching downstream
circuits. Type 1+2 combines both protection functions.
For many distribution-board applications, a surge
protection device type 2 is the practical choice. Type 2 SPDs are
tested with an 8/20 μs current waveform and are designed to discharge a surge
current while limiting the voltage applied to connected equipment.
Do not choose by kA alone
Check the SPD's core electrical ratings against the actual
installation. Uc, or maximum continuous operating voltage, must match the
system voltage and earthing arrangement.
Up, or voltage protection level, indicates the voltage level
limited across the SPD terminals during the specified test condition. It should
remain suitable for the protected equipment's withstand capability. In, or
nominal discharge current, indicates the rated surge current for the specified
test. Imax, or maximum discharge current, shows the device's higher
surge-handling capability.
A surge protection device Type 2 should
therefore be selected using its complete rating information, not one headline
number.
Match the SPD to the installation
System configuration matters. Confirm whether the
application is single-phase or three-phase, identify the required protection
modes, and check the installation and upstream protection requirements. Axis
provides Type 1, Type 1+2 and Type 2 options for both single- and three-phase
applications.
Connection details matter too. Keep SPD connecting
conductors as short as practical. Longer wiring can reduce the SPD's
effectiveness during a fast surge. Correct earthing and compliance with the
manufacturer's installation instructions are essential.
A surge
protection device spd should also be coordinated with the site's
wider lightning protection arrangement, particularly where electrical circuits
cross Lightning Protection Zones.
Use a clear selection checklist
Before selecting a surge protection device type 2, check:
- System
voltage
- Earthing
arrangement
- Installation
location
- Uc
- Up
- In
- Imax
- Single-phase
or three-phase configuration
- Upstream
protection requirements
- Need
for downstream Type 3 protection
For a surge protection device spd matched
to the actual installation rather than a generic specification, review the
electrical system, protection zones and required performance with a qualified
electrical professional. Sensitive electronic equipment may also require
additional downstream Type 3 protection.
Protecting your electrical system starts with the right
SPD
The right SPD depends on the system it is protecting. Axis
India offers Type 1, Type 1+2 and Type 2 surge protection solutions for
different electrical applications. Review the system requirements, compare the
ratings, and choose the protection that fits the installation.
Frequently asked questions
Where is a Type 2 SPD normally installed?
A surge protection device type 2 is
commonly installed at a main or sub-distribution board to limit transient
overvoltages on downstream circuits.
Is a Type 2 SPD suitable for every building?
No. Selection depends on lightning exposure, the building's
protection system, installation arrangement and applicable risk assessment.
Which SPD is best for a distribution board?
A surge protection device Type 2 is
commonly used at distribution boards to limit transient overvoltages and
protect downstream circuits. The final selection depends on the electrical
system, surge exposure and overall protection arrangement.
What is the difference between Uc and Up?
Uc is the maximum continuous operating voltage. Up is the
voltage protection level during the specified surge test.
How should SPD ratings be compared?
Check Uc, Up, In and Imax against the electrical system and
installation conditions. A surge protection device (SPD) should
be selected as a complete protection solution, not by kA capacity alone.